Vici Two Position Microelectric Manual do Utilizador Página 1

Consulte online ou descarregue Manual do Utilizador para Hardware Vici Two Position Microelectric. VICI Two Position Microelectric User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 6
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
1
Two Position Microelectric
Valve Actuator
(Control module serial numbers starting with EM2C)*
The microelectric actuator consists of a control module, a stepper motor/gearbox assembly, a manual
controller (use is optional), a universal AC input (100-240 VAC, 50-60 Hz) to 24 VDC power supply,
and the interconnecting cables. The actuator is self-adjusting from 30° to 90° – no valve alignment is
necessary. Once a valve is installed by tightening the clamp screw, the actuator senses the positive
stops within the valve and memorizes them in the first four moves.
The time it takes a valve to cycle from Position A to Position B
depends on the amount of rotation involved. To determine the
number of degrees in the angle of rotation, divide 360° by the
number of ports in the valve. Then consult the table at right.
Installation and Use
Getting Started
Figure 1 on the next page shows how to connect the various actuator components. There are four
connectors on the control module, keyed and sized to prevent incorrect connection.
Cable and Connector Functions
Input power
(20-30 VDC, with 24-28 VDC preferred) is supplied through
a coaxial connector: the inner pin is + voltage and the outer pin is ground.
The average DC current requirement is 2.5 amps. Standby current draw
is 60 milliamps. The actuator should not share a power supply with
other noise-sensitive electronics, as the high current draw can cause
problems.
Motor driver output
is through the five-pin connector: pins 1, 2, 4, and 5
carry the stepper motor phase drive signals. Pin 3 is grounded and
tied to the cable shield to reduce electrical noise.
A three-pin connector is used for the
RS-232 interface
: pin 1 is ground,
pin 2 is transmit to the host computer, and pin 3 is receive from the
host. (A discussion on serial control of the actuator starts on page 3.)
The ten-pin connector is for the
manual controller
or for
digital input/output signals
; the actuator can be
controlled by
either
or
both
. The manual controller has a through port, so an additional cable can
provide simultaneous control by an external system. (Digital control of the actuator is discussed on
page 3.)
Technical Note 413
Valco Instruments Co. Inc.
Pin # Signal Description
Input Power Cable
inner +20-30 VDC power
outer Ground
Motor Driver Output Cable
1 Phase B
2 Phase B
3 Ground
4 Phase A
5 Phase A
36°
45°
60°
90°
70
85
110
145
90
115
150
235
EH EP
330
410
500
710
ET
140
175
235
300
ED
60
70
85
115
EQ
Switching times in milliseconds
* Serial numbers are on the underside of the control module. (Figure 2) Actuators of this series are further identified by a metallic
control module housing. If your actuator control module has a plastic housing and a serial number starting with E2CA, please refer to
Technical Note 421.
Vista de página 0
1 2 3 4 5 6

Resumo do Conteúdo

Página 1 - Valve Actuator

1Two Position MicroelectricValve Actuator (Control module serial numbers starting with EM2C)*The microelectric actuator consists of a control module,

Página 2 - POSITION

22 POSITION ACTUATORCONTROL MODULEABPOSITIONAPOSITIONBPOSITIONTO 110 OR 220 VAC(User must supply otherline cord configurations)POWER SUPPLYP/N PS24VDC

Página 3 - Input Modes

3MountingThe actuator should be oriented so that any potential leakage of liquidfrom the valve or fittings flows away from rather than into the actuat

Página 4 - Serial Communication Protocol

4Position B. Operation in this mode requires two relays, as shown inthe illustration at right. Relays should be asserted (turned on) fora minimum of

Página 5

5With the software-settable device “ID” feature enabled, the serial port output (transmit line) of theactuator is disabled (high impedance). Thus, as

Página 6 - RS-485 Option

®®North America, South America, and Australia/Oceania contact: Europe, Asia, and Africa contact:Valco Instruments Co. Inc. VICI AG InternationalChemin

Comentários a estes Manuais